Step 3 Disconnect cables from the faulty VESDA batteries.
Step 4 Use a Phillips screwdriver to remove screws on the battery protective panel, and remove the
protective panel.
Step 5 Replace the batteries, and connect battery cables.
Distinguish the positive and negative battery terminals when connecting battery cables.
Figure 4-43 Connecting battery cables
Step 6 Reinstall the battery protective panel.
Figure 4-44 Installing the battery protective panel
Step 7 Check whether the new VESDA batteries are working properly.
Turn on the standby power switch. If the power fault indicator is off, the batteries are working properly.
----End