FusionModule1000A20 Prefabricated All-in-One Data
Center
Maintenance Guide
Check Item
Description
ALM indicator

3.5.4 Fire Extinguishing System (CE)

Table 3-14 Semi-annual maintenance checklist for the fire extinguishing system
Device
Operation
Fire
Commission the fire
extinguishing
extinguishing system by
system
following the
commissioning
instructions in the Fire
Extinguishing System
Commissioning (CE)
section in the
commissioning guide
for the solution in use.
Fire alarm bell
Flip the key to Enable
Control on the
extinguishant control
panel rightward. Press
Silence/Sound Alarm
to start or abort the fire
alarm bell. Reset the
key to Enable Control
Issue 01 (2019-07-15)
Criteria
blinks at super short
intervals for 0.5s
(blinking at 10 Hz, on
for 0.05s and then off for
0.05s) and then turns off
for 0.5s. The cycle lasts
for 10s.
Steady on: A fault alarm
is raised.
Off: No fault alarm is
raised.
Semi-annual maintenance of the fire extinguishing system involves system commissioning.
Before the maintenance, inform the related administrative departments that the fire
extinguishing system will be maintained and stop working.
Before maintaining the fire extinguishing system, remove the electrical actuator from the
container valve of the fire cylinder. This prevents the extinguishant release due to
misoperations, and prevents accidental damage.
After the maintenance, reconnect the electrical actuator, and inform the administrative
departments that the fire extinguishing system has become operational.
Check Standard
Devices work properly,
and the management
system displays related
alarms.
The alarm bell rings
normally. The alarm bell
rings loud and clear when
it is started.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
See ECC800 Data Center Controller
V100R001C30 User Manual to handle
alarms, or contact Huawei technical port.
Maintenance Guide
Replace the corresponding
component.
1. Check and reconnect cables to
the fire alarm bell.
2. If the fault persists, replace the
fire alarm bell.
3 Routine Maintenance
24