Fire Extinguishing System (Ce) - Huawei FusionModule1000A40 Maintenance Manual

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Maintenance Guide
Device
Method
Fire
Check the
extinguisher
appearance of the
fire cylinder,
electromagnetic
valve, pipeline, and
nozzle.
Read the pressure
shown on the
pressure gauge.
Emergency
Switch off the power
light
circuit breaker.
Smoke
Check the smoke
detector
detector indicator.
Heat
Check the heat
detector
detector indicator.

3.4.5 Fire Extinguishing System (CE)

Table 3-7 Monthly maintenance checklist for the fire extinguishing system
Device
Operation
Extinguishant
Check indicators on
control panel
the extinguishant
control panel.
Issue 04 (2021-02-10)
Check Standard
All devices of
the fire
extinguisher are
intact, free from
deformation and
mechanical
damage.
All devices of
the fire
extinguisher are
free from rust
on the exterior,
and the coating
is intact.
The lead seal
and safety signs
on hand-
operated devices
are intact.
The pressure
pointer is in the
green zone.
The emergency
light turns on.
The indicator
blinks once
every 6s.
The indicator
blinks once
every 6s.
Check Standard
The power indicator
turns on, and the
alarm indicator turns
off.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Replace the fire cylinder by following
instructions in "Replacing a Fire
Cylinder." For details about how to
replace other devices, contact Huawei
technical support.
Repaint the device.
Replace the electromagnetic valve.
Ask a local maintenance engineer to
check whether the fire cylinder leaks
extinguishant. If leakage occurs, the
maintenance engineer asks the fire
extinguisher manufacturer to recharge
the extinguishant.
Replace the device.
Replace the smoke detector.
Replace the heat detector.
Maintenance Guide
Replace the extinguishant control
panel.