If the red indicator blinks once every 6s, the heat detector is working properly.
----End
Follow-up Procedure
Dispose of the removed heat detector that is confirmed faulty.

5.4.1.4 Replacing an Input/Output Module

Prerequisites
A spare input/output module of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Prerequisites
Tools: Phillips screwdriver, protective gloves
Material: input/output module
Documents: fire extinguishing drawings and parameters
Skill requirement: fire engineer
Before replacing the input/output module, inform the related administration
department of the temporary downtime of the fire extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
1.
2.
3.
4.
5.
6.
Issue 04 (2021-02-10)
NO TE
NO TICE
Switch off the active and standby power supplies to the fire alarm control
panel.
Open the cover of the input/output module and remove it.
Remove cables from the input/output module
Remove the screws on the bottom box using a Phillips screwdriver, and
remove the box.
Insert the output plug of the encoder into the encoding socket of the new
input/output module, adjust the encoder to the encoding function, set the
original address, and press the Execute button to complete the address
encoding.
Install the new input/output module, connect the cables, and install the cover.