5.4.1.5 Replacing a Gas Release Indicator
Prerequisites
A spare gas release indicator of the same model is available and functional.
Impact on the System
The fire extinguishing system stops working during the replacement.
Prerequisites
Tools: Phillips screwdriver, protective gloves, step ladder, flat-head screwdriver
Material: spare gas release indicator
Document: fire extinguishing device layout diagram (standard)
Skill requirement: fire engineer
Before replacing the gas release indicator, inform the related administration
department of the temporary downtime of the fire extinguishing system. After the
replacement, inform the administration department that the system has become
operational.
Procedure
Step 1 Switch off the active and standby power supplies to the fire alarm control panel.
Step 2 Remove the screws shown in
the panel.