Huawei FusionModule1000A40 Maintenance Manual page 51

Prefabricated all-in-one data center
Hide thumbs Also See for FusionModule1000A40:
Table of Contents

Advertisement

FusionModule1000A40 Prefabricated All-in-One
Data Center
Maintenance Guide
Alarm
Alarm
Indicator
Type
Name
Fire In Zone
Alert
2
alarm
Zone Fault/
Fault/
Test/
Isolatio
Disablemen
n alarm
t 1
Zone Fault/
Fault/
Test/
Isolatio
Disablemen
n alarm
t 2
Zone Fault/
Fault/
Test/
Isolatio
Disablemen
n alarm
t 3
Extinguisha
Isolatio
nt
n alarm
Manual
Isolatio
Release
n alarm
1st Stage
Isolatio
Contact
n alarm
Issue 04 (2021-02-10)
Alarm
System Action
Severity
Major
the FIRE RELAY
port become
closed, while NC
and C become
open.
2. S3 is triggered
to output 24 V
DC voltage
when both
smoke and heat
detectors raise
alarms.
Meanwhile, NO
and C on the
2nd Stage port
become closed,
while NC and C
become open.
Minor
If there is a fault,
NO and C on the
FAULT RELAY port
become closed,
while NC and C
Minor
become open.
Minor
Major
The system has
entered the
extinguishant
releasing phase.
Major
The system is
manually started to
enter the
extinguishant
releasing phase.
Major
The S1 port has 24
V DC voltage
output.
Copyright © Huawei Technologies Co., Ltd.
4 Common Faults and Troubleshooting Measures
Possible
Causes
The smoke or
heat detector
in zone 2 raises
an alarm.
Zone 1 is
isolated, faulty,
or in test
mode.
Zone 2 is
isolated, faulty,
or in test
mode.
Zone 3 is
isolated, faulty,
or in test
mode.
Extinguishant
is in isolation
mode.
Manual
Release is in
isolation mode.
1st Stage
Contact is in
isolation mode.
Solution
Check the end
resistor, cable
connections, and
devices of the
relevant loop.
Reset relevant
devices to restore the
system to normal.
44