Fire Extinguishing System (Ce) - Huawei FusionModule1000A20 Maintenance Manual

Ct solution
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 CT Solution
Maintenance Guide
Check
Item
Pad
Exit button

3.4.4 Fire Extinguishing System (CE)

Table 3-7 Monthly maintenance checklist for the fire extinguishing system
Device
Extinguisha
nt control
panel
Issue 01 (2019-02-25)
Operation
Check Standard
RF_Z
On: No network
indicator
parameters exist. A
network is waiting
to be created.
Blinking slowly: A
network is set up,
and node access is
not allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
Blinking at super
short intervals: A
network is set up,
and node access is
allowed (the
indicator blinks at
10 Hz, on for 0.05s
and then off for
0.05s).
Blinking at super
short intervals
intermittently: The
device is searching
for a network (the
indicator blinks at 2
Hz, on for 0.5 and
then off for 0.5s).
Exterior
The exterior is
intact and the
touchscreen is
working properly.
Function
The function is
normal.
Operation
Check indicators
on the
extinguishant
control panel.
Copyright © Huawei Technologies Co., Ltd.
Troubleshooting
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to register the device, or
contact Huawei technical support.
Replace the pad.
Replace by following instructions in
5.3.10.2 Replacing an Exit Button.
Check Standard
The power indicator
turns on, and the
alarm indicator
turns off.
3 Routine Maintenance
Maintenance Guide
Replace by following
instructions in 5.4.1.10
Replacing the Extinguishant
Control Panel (CE).