Other Systems - Huawei FusionModule1000A20 Maintenance Manual

Ct solution
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 CT Solution
Maintenance Guide
Device
VESDA
power
supply

3.6.5 Other Systems

Table 3-18 Semi-annual maintenance checklist for other systems
Item
Lights
Ventilation
vent air
filter
Cable trays
inside
containers
Cables
Issue 01 (2019-02-25)
Operation
Check Standard
Check the power
The power indicator
indicator.
turns on.
Method
Check whether the
lights can be
switched on
normally.
Check whether the
filter is blocked.
Check whether the
cable trays are
securely connected
without damage or
misshapen.
Check cable
connections.
Copyright © Huawei Technologies Co., Ltd.
Check
Troubleshooting
Standard
1. If a light cannot be switched on,
The lights turn
check whether the light is
on normally.
securely installed and in good
contact with the light base.
2. If a light is securely installed and
in good contact with the light
base but fails to turn on, replace
the light.
The air filter is
If an air filter is slightly blocked,
not blocked.
clean the air filter and reinstall it. If
more than 50% of the meshes are
blocked, replace the air filter.
Cable trays are
Secure cable trays that have become
properly
loose.
installed, and
fasteners are
secure.
Cable trays,
Repaint corroded cable trays, or
screws, and
replace damaged and seriously
nuts are free
corroded parts. For details, see the
from rust or
installation guide for the
corrosion.
corresponding solution.
Cables are
Secure terminal connections, and
securely
replace terminals that do not meet
connected
requirements. For details, see the
without bare
installation guide for the
terminals.
corresponding solution.
3 Routine Maintenance
Maintenance Guide
1. Check the power cables.
2. Replace by following
instructions in 5.4.2
Replacing Batteries for the
VESDA Power Box.