FusionModule1000A20 CT Solution
Maintenance Guide

3.4.3 Monitoring System

Table 3-5 Monthly maintenance checklist for the monitoring system
Check
Item
Combined
module
Access
actuator
Issue 01 (2019-02-25)
Operation
Check Standard
INPUT1
The green indicator
indicator
is steady on.
INPUT2
The green indicator
indicator
is steady on.
OUTPUT
The green indicator
indicator
is steady on.
Power input
Dual-input voltage
range: 43–58 V DC;
rated voltage: 53.5
V DC
Power output
Voltage range:
43–58 V DC; rated
voltage: 53.5 V DC
Temperature: –20° C
Operating
environment
to +65° C
Humidity: 5–95%
RH
(non-condensing)
Power input
Input voltage:
36–60 V DC
PWR
Steady on: The
indicator
power supply is
normal.
Off: No power
supply is available.
ALM
Steady on: A fault
indicator
alarm is generated.
Off: No fault alarm
is generated.
Copyright © Huawei Technologies Co., Ltd.
3 Routine Maintenance
Troubleshooting
Check the mains and the input power
cables.
NOTICE
Before replacing the combined module,
verify that it is powered off and all three
indicators are off.
If the input voltage is abnormal,
check the power grid and input cable
connection.
For details, contact Huawei technical
support.
Check that the ambient temperature
and humidity for the combined
module are normal.
Check the input power cables if the
input voltage is abnormal.
Check the input power cables.
Refer to ECC800 Data Center
Controller V100R001C30 User
Manual to handle alarms, or contact
Huawei technical support.