Ac Actuator Alarms - Huawei FusionModule1000A20 Maintenance Manual

Ct solution
Hide thumbs Also See for FusionModule1000A20:
Table of Contents

Advertisement

FusionModule1000A20 CT Solution
Maintenance Guide
Alarm Name
PoE2 output
overload
PoE3 output
overload
PoE4 output
overload
Communication
failure

4.3.4 AC Actuator Alarms

Alarm Name
Communication
Failure
Overcurrent Alarm
Relay 1 Life Pre
Alarm
Issue 01 (2019-02-25)
Alarm
Possible Cause
Severity
Major
The second output is
overloaded or the second
power supply pin is
short-circuited.
Major
The third output is
overloaded or the third
power supply pin is
short-circuited.
Major
The fourth output is
overloaded or the fourth
power supply pin is
short-circuited.
Critical
The PoE communication
is interrupted.
Alarm
Possible Cause
Severity
Critical
The wireless
communication (802.15.4)
is interrupted.
Major
The load is
short-circuited.
Warning
The use duration for relay
1 reaches the forewarning
threshold.
Copyright © Huawei Technologies Co., Ltd.
4 Alarms and Faults
Solution
1. Check that the second
output is not
overloaded.
2. Check that the second
power supply pin is not
short-circuited.
1. Check that the third
output is not
overloaded.
2. Check that the third
power supply pin is not
short-circuited.
1. Check that the fourth
output is not
overloaded.
2. Check that the fourth
power supply pin is not
short-circuited.
Check that cables are
correctly connected for the
smart ETH gateway, and
that the RUN indicator of
the smart ETH gateway is
blinking normally.
Solution
1. Check the wireless
communication
(802.15.4) is
interrupted.
2. Check that the wireless
indicator on the AC
actuator is normal.
3. Reconnect the AC
actuator.
Check that the load is not
short-circuited.
Contact Huawei technical
support.
57

Advertisement

Table of Contents
loading