Parts Replacement For The Intelligent Battery Monitoring System; Replacing An Ibox - Huawei FusionModule2000 Maintenance Manual

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Figure 5-48 Electronic lock
Step 3 Install a new electronic lock and connect the monitoring cable to the new lock.
Step 4 Log in to the ECC800-Pro WebUI and choose System Settings > Access
Management. Set the access permission for the new electronic lock according to
the access permission setting for the faulty electronic lock. Then perform the
Synchronize to Device operation.
Step 5 On the ECC800-Pro WebUI, choose Monitoring > System > ECC800 > Controls >
Delete device with communication failure, and click Submit.
Step 6 Check that the electronic lock functions properly.
----End
5.4.4 Parts Replacement for the Intelligent Battery Monitoring
System

5.4.4.1 Replacing an iBOX

Impact on the System
The battery data cannot be monitored.
Preparations
Procedure
Step 1 Clear the network parameters for all the iBATs managed by the iBOX to be
replaced.
Issue 01 (2020-12-25)
Material: iBOX
Skill requirement: hardware installation engineers
Copyright © Huawei Technologies Co., Ltd.
5 Parts Replacement
97