Huawei FusionModule2000 Maintenance Manual page 117

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Figure 5-61 Installing a T/H sensor
Step 6 Set the DIP switch on the T/H sensor.
Table 5-11 DIP switch settings on T/H sensors
Locati
on
Cold
aisle
Hot
aisle
Issue 01 (2020-12-25)
Display Name
Addr
ess
Cold aisle 1
11
temp/humid
Cold aisle 2
12
temp/humid
Cold aisle 3
13
temp/humid
Cold aisle 4
14
temp/humid
Cold aisle 5
15
temp/humid
Hot aisle 1
21
temp/humid
Copyright © Huawei Technologies Co., Ltd.
DIP Switch No.
1
2
3
ON
ON
OFF
OFF
OFF
ON
ON
OFF
ON
OFF
ON
ON
ON
ON
ON
ON
OFF
ON
5 Parts Replacement
4
5
6
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
ON
OFF
OFF
OFF
ON
OFF
110