FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Item
Indicators on the
access actuator
Availability of the
cabinet electronic
lock

3.5 Semiannual Maintenance

Table 3-8 Semiannual maintenance for the power supply and distribution system
Item
UPS cleanliness
Issue 01 (2020-12-25)
Method
Observe the
PWR, RUN,
and ALM
indicators.
Open and
close the
cabinet
door, and
view alarm
information
on the
ECC800-Pro
WebUI.
Method
Visual inspection
Copyright © Huawei Technologies Co., Ltd.
Expected Result
● If the PWR
indicator is
steady green,
the power input
is normal.
● The RUN
indicator blinks
at long
intervals,
indicating that
the device is
running
properly.
● The ALM
indicator is off.
The door status
sensor alarm
information can
be queried on the
ECC800-Pro
WebUI.
Expected Result
The white paper
that you use to
wipe the cabinet
panel is clean.
3 Routine Maintenance
Troubleshooting
● If the PWR indicator
is off, check
whether the
communications
cable is loose or
disconnected or
whether the smart
ETH gateway is not
energized. If so,
reconnect the cable.
If not, replace the
actuator.
● If the RUN indicator
blinks at short
intervals, check
whether the
communications
cable is normal. If
not, replace the
cable.
● If the ALM indicator
is steady on, check
for alarms.
If no alarm is
generated after the
door with a door status
sensor installed is
opened, replace the
door status sensor.
Troubleshooting
If the white paper
becomes dirty,
clean up the dust,
especially from
the air filter on
the front door, or
replace the air
filter.