Huawei FusionModule2000 Maintenance Manual page 46

Smart modular data center
Hide thumbs Also See for FusionModule2000:
Table of Contents

Advertisement

FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Item
Availability
of the
UIM20A
expansion
module
Availability
of the rack
environment
unit
Issue 01 (2020-12-25)
Method
On the ECC800-
Pro WebUI,
choose
Monitoring >
Cabinet > IT
Cabinet > UIM
Group > UIM1.
On the Running
Info page, check
information such
as
communication
status and
temperature.
On the ECC800-
Pro WebUI,
choose
Monitoring >
Cabinet >
System > Rack
Environment
Unit. On the
Running Info
page, check
information such
as
communication
status and
temperature.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
On the ECC800-Pro
WebUI, you can see
that the UIM20A
expansion module
communicates
properly and the
temperature is
displayed properly.
On the ECC800-Pro
WebUI, you can see
that the rack
environment unit
communicates
properly and the
temperature is
displayed properly.
3 Routine Maintenance
Troubleshooting
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
UIM20A expansion
module.
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
rack environment
unit.
39