FusionModule2000 Smart Modular Data Center
Maintenance Guide (Fusion Module Actuator)
Item
Cleanliness of the
smart cooling
product
Outdoor fan
Table 3-10 Semiannual maintenance for the management system
Item
Availability
of the smart
ETH gateway
Issue 01 (2020-12-25)
Method
Visual inspection
Visual inspection
Method
On the ECC800-
Pro WebUI,
choose
Monitoring >
System > Smart
ETH Gateway
Group > Smart
ETH Gateway.
On the Running
Info page, view
the
communication
status, PoE port
connection, and
power supply
status.
Copyright © Huawei Technologies Co., Ltd.
Expected Result
The white paper
that you use to
wipe the cabinet
panel is clean.
● The fan runs
properly
without
abnormal noise
or vibration,
and the blades
rotate properly.
● Cables are not
damaged or
aged.
Expected Result
The connection
status and power
supply status of the
PoE port on the
smart ETH gateway
can be queried on
the ECC800-Pro
WebUI.
3 Routine Maintenance
Troubleshooting
If the white paper
turns black, clean
the smart cooling
product cabinet.
● Power off the
outdoor unit
and replace
the fan
component.
● Power off the
outdoor unit
and replace
cables.
Troubleshooting
If the display is
abnormal, check
whether the
communications
cable is loose or
disconnected. If so,
reconnect the cable.
If not, replace the
smart ETH gateway.
38