Routine Maintenance; Ups Maintenance - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)

7.1 UPS Maintenance

Operating Environment Checklist
No.
Check Item
1
Equipment
room
environment
2
Rodent-proof
Issue 02 (2024-01-05)
7
Acceptance Criteria
● The fireproof door of
the equipment room
remains closed, and the
air conditioner works
normally without
interruption.
● The equipment room is
airtight, and the
equipment is not in a
direct ventilation
environment.
● There is no dust or
flammable sundries in
the equipment room.
Rodent-proof measures
are taken in the
equipment room, such as
rat guard and rat trap.
Copyright © Huawei Digital Power Technologies Co., Ltd.

Routine Maintenance

Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
7 Routine Maintenance
Check
Interval
Monthly
Monthly
97