Faqs; Transferring To Bypass Mode Manually; Performing Epo - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)

9.1 Transferring to Bypass Mode Manually

Before you shut down the inverter, ensure that the bypass is normal. If the bypass
is abnormal, after you shut down the inverter, the UPS supplies no power, and the
loads are powered off.
Shut down the inverter on the LCD or WebUI. The UPS automatically transfers to
bypass mode.

9.2 Performing EPO

Prerequisites
Choose Monitoring > UPS System > Running Parameter > System Settings on
the WebUI and set EPO detection to Enable.
● After you press the EPO button, the UPS supplies no power, and the loads
● If the UPS is in maintenance bypass mode, the UPS still supplies power after
Issue 02 (2024-01-05)
NO TICE
NO TE
If you shut down the inverter when the bypass input voltage or frequency exceeds the
specified threshold, the UPS supplies no power, and the loads are powered off.
NO TICE
powers off.
you press the EPO button.
Copyright © Huawei Digital Power Technologies Co., Ltd.

9 FAQs

9
FAQs
115