Installing Cabinets, Enclosure Frames, Copper Bars, And Cables; Ups Cable Connection Reference - Huawei FusionPower6000 UPS5000-H-600 kVA-FT User Manual

Hide thumbs Also See for FusionPower6000 UPS5000-H-600 kVA-FT:
Table of Contents

Advertisement

UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Figure 4-1 Removing the pallet
----End
4.2 Installing Cabinets, Enclosure Frames, Copper Bars,
and Cables
For details about the procedure and requirements for installing cabinets, enclosure
frames, copper bars, and cables, see the corresponding FusionPower6000 user
manual.

4.3 UPS Cable Connection Reference

Context
● When preparing cables, keep away from the cabinets to prevent cable scraps
● After installing cables, clean the cabinet top, bottom, copper bar wiring
● Prepare terminals onsite. The length of the copper wire should be the same as
Procedure
Step 1 Route a cable into the cabinet and bind it to a nearby beam.
Step 2 Pull the cable to the copper bar to which the cable is to be connected, determine
the cable length, and mark the cable at the position where the cable is to be cut.
Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position,
strip the cable, and crimp a terminal.
Issue 02 (2024-01-05)
WARNING
from entering the cabinets. Cable scraps may cause sparks during power-on
and cause personal injury or device damage.
positions, and other positions. Ensure that there is no dust or scraps inside and
around cabinets.
that of the part of the terminal that covers the conductor.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 Installation
67