UPS5000-H-600 kVA-FT(M)
User Manual (FusionPower6000)
Item
Dimensions (H x W x
D)
Weight
2.5.2 Bypass Module
The UPS supplies power through the bypass under the following circumstances:
●
●
●
●
●
Figure 2-9 Appearance
(1) Auxiliary power supply
(4) Fault indicator (FAULT)
(7) Battery cold start button
Table 2-6 Indicator description
Silk Screen
Name
NORMAL
Running
indicator
Issue 02 (2024-01-05)
The S-ECO or ECO mode is used and the bypass voltage is within the specified
range.
The power module overload times out.
Both active and standby energy control modules (ECMs) in the system are
abnormal.
The system fails to run properly and transfers to bypass mode.
The power supply is switched to the bypass manually.
Color
Green
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
130 mm x 442 mm x 750 mm
< 55 kg
(2) Crowbar
(5) Alarm indicator (ALM)
(8) Positioning lock
Description
● Steady on: The bypass supplies power.
● Blinking at intervals of 5s (on for 2.5s and then
off for 2.5s): The bypass does not supply power.
● Blinking at intervals of 0.25s (on for 0.125s and
then off for 0.125s): The bypass is not configured
or the software is being upgraded.
● Off: The bypass software is being upgraded.
2 Product Overview
(3) Ready switch
(6) Running indicator
(NORMAL)
33