A800 - Mitsubishi Electric FR-A800 Series Beginner's Manual

Hide thumbs Also See for FR-A800 Series:
Table of Contents

Advertisement

Appendix
Param-
Name
eter
81
Number of motor poles
82
Motor excitation current
83
Rated motor voltage
84
Rated motor frequency
Speed control gain
89
(Advanced magnetic flux
vector)
90
Motor constant (R1)
91
Motor constant (R2)
Motor constant (L1)/d-
92
shaft inductance (Ld)
Motor constant (L2)/q-
93
shaft inductance (Lq)
94
Motor constant (X)
Online auto tuning
95
selection
Auto tuning setting/
96
status
100
V/F1 (first frequency)
V/F1 (first frequency
101
voltage)
102
V/F2 (second frequency)
V/F2 (second frequency
103
voltage)
104
V/F3 (third frequency)
V/F3 (third frequency
105
voltage)
106
V/F4 (fourth frequency)
V/F4 (fourth frequency
107
voltage)
108
V/F5 (fifth frequency)
V/F5 (fifth frequency
109
voltage)
Third acceleration/
110
deceleration time
111
Third deceleration time
Frequency Inverters - Beginner's Guide
Setting Range
Initial Value
2, 4, 6, 8, 10, 12,
9999
9999
0–500 A, 9999
0–3600 A,
9999
9999
0–1000 V
200/400 V
10–400 Hz, 9999
9999
0–200 %, 9999
9999
0–50 Ω, 9999
/
0–400 mΩ,
9999
9999
–50 Ω, 9999
/
0–400 mΩ,
9999
9999
0–6000 mH,
9999
/
9999
0–400 mH,
9999
0–6000 mH,
9999
9999
0–400 mH,
9999
0–100 %, 9999
9999
0–2
0
0, 1, 11, 101
0
0–590 Hz, 9999
9999
0–1000 V
0 V
0–590 Hz, 9999
9999
0–1000 V
0 V
0–590 Hz, 9999
9999
0–1000 V
0 V
0–590 Hz, 9999
9999
0–1000 V
0 V
0–590 Hz, 9999
9999
0–1000 V
0 V
0–3600 s, 9999
9999
0–3600 s, 9999
9999
Param-
Name
eter
112
Third torque boost
Third V/F (base
113
frequency)
Third stall prevention
114
operation level
Third stall prevention
115
operation frequency
Third output frequency
116
detection
PU communication
117
station number
PU communication
118
speed
PU communication stop
119
bit length / data length
PU communication parity
120
check
Number of PU
121
communication retries
PU communication check
122
time interval
PU communication
123
waiting time setting
PU communication CR/LF
124
selection
Terminal 2 frequency
setting gain frequency
125
Simple
Simple
Simple
Terminal 4 frequency
setting gain frequency
126
Simple
Simple
Simple
PID control automatic
127
switchover frequency
128
PID action selection
129
PID proportional band
130
PID integral time
131
PID upper limit
132
PID lower limit
133
PID action set point
Parameter list (FR-A800)
Setting Range
Initial Value
0–30 %, 9999
9999
0–590 Hz, 9999
9999
0–400 %
150 %
0–590 Hz
0 Hz
0–590 Hz
60/50 Hz
0–31
0
48, 96, 192, 384,
192
576, 768, 1152
0, 1, 10, 11
1
0–2
2
0–10, 9999
1
0, 0.1–999.8 s,
9999
9999
0–150 ms, 9999
9999
0–2
1
0–590 Hz
60/50 Hz
0–590 Hz
60/50 Hz
0–590 Hz, 9999
9999
0, 10, 11, 20, 21,
40–43, 50, 51, 60,
61, 70, 71, 80, 81,
90, 91, 100, 101,
0
1000, 1001,
1010,1011, 2000,
2001, 2010,2011
0.1–1000 %,
100%
9999
0.1–3600 s, 9999
1s
0–100 %, 9999
9999
0–100 %, 9999
9999
0–100 %, 9999
9999
A - 3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a820Fr-a840Fr-a842Fr-a846

Table of Contents