6.4 Replacing the CMU Module
This section describes how to replace the existing CMU module (one of the models LQP520,
LQP525, or LQP527) with a new one (of that same model).
6.4.1 Replacing the module
What you should get in preparation
① Personal computer (with S10V Base System installed in it)
② RS-232C cable (used, along with the S10V Base System, for connection to the LPU
module's RS-232C interface port)
③ CMU module (LQP520/525/527)
④ 10BASE-T cross cable (used, along with the S10V Base System, for connection to the
CMU module's ET.NET interface port)
⑤ Application programs and setup information stored in the CMU module's memory
Replacement procedure
① Take a note of the following switch setting(s) provided on the existing CMU module's
front panel: the T/M switch setting if the CMU module is of model LQP520; or the ST No.
and BATT.SEL switch settings if it is of model LQP525 or LQP527.
② Take a note of the LADDER and T/M switch settings provided on the LPU module's front
panel.
Power
supply
RS-232C cable
LPU
RS-232C
ET.NET
ET.NET cable
Battery connector
(provided only with the
models LQP525 and
LQP527)
6-49
6 MAINTENANCE
LPU module's toggle and
rotary switches setting
LADDER
RUN
STOP
T/M
RESET
ON
OFF
LQP520 module's toggle
and rotary switches setting
T/M
U
ST.No.
L
LQP525/527 module's toggle
and rotary switches setting
BATT.SEL
U
ST.No.
L