Table 6-3 Cpu Module Error Indications And Remedies (2) - Hitachi LQE550 User Manual

Cpu link for s10mini and s10v
Table of Contents

Advertisement

Table 6-3 CPU Module Error Indications and Remedies (2)

CPU module
No.
indication
(S10mini)
CPL▲ TRM
9
CPL▲ △.
10
No number
11
(between 1 and
10) appears.
• The value in the △ mark position indicates the internal program version number. The value in
the □ mark position represents the leftmost digit of the revision number.
• Either the ▲ mark or ■ mark appears to indicate whether the main module or sub-module is
affected. (When the S10V is used, the tool system gives this type of indication.)
Error code
(S10V)
Link line error:
A reception error occurred
0x00E0
successively or intermittently in G-
register area transfer.
System program operating normally:
0x0080
The CPU link module is operating
normally.
(None):
The CPU link module is not normally
None
started due, for instance, to damaged
data in the ROM.
MAIN/SUB selector switch
"0" (MAIN)
"1" (SUB)
Error description
M
S
6-9
6 MAINTENANCE
Action
• Check that the link cable extension
length is within the specified limit.
For the specified limit, see
"1.2 Specifications."
• Check that the link cable and crimp
terminals are not broken or partly
broken.
• Check for improper terminating
resistor setup. For the setup
procedure, see "2.1 Names and
Functions of Each Part."
A normal operation is indicated.
No error is encountered.
• Hold the CPU or LPU RESET
switch in the ON position for a
period of longer than one second
and then release it.
• If the indication does not go off,
replace the CPU link module
because it is defective.