Mitsubishi Electric 800 Series Instruction Manual page 43

Rs-485 interface board, rs-485 communication terminals
Hide thumbs Also See for 800 Series:
Table of Contents

Advertisement

• Error code
If any error is found in the data received by the inverter, its error definition is sent back to the computer together with the
NAK code.
Error
Error Item
Code
H0
Computer NAK error
H1
Parity error
H2
Sum check error
H3
Protocol error
H4
Framing error
H5
Overrun error
H6
H7
Character error
H8
H9
HA
Mode error
HB
Instruction code error
HC
Data range error
HD
HE
HF
Normal (no error)
42
PARAMETER
Error Description
The number of errors consecutively detected in communication request
data from the computer is greater than the permissible number of retries.
The parity check result does not match the specified parity.
The sum check code in the computer does not match that of the data
received by the inverter.
The data received by the inverter has a grammatical mistake. Or, data
receive is not completed within the predetermined time. CR or LF is not
as set in the parameter.
The stop bit length differs from the initial setting.
New data has been sent by the computer before the inverter completes
receiving the preceding data.
The character received is invalid (other than 0 to 9, A to F, control code).
Parameter write was attempted in other than the computer link operation
mode, when operation command source is not selected or during inverter
operation.
The specified instruction code does not exist.
Invalid data has been specified for parameter writing, running frequency
setting, etc.
Inverter Operation
Trips (E.SER) if error occurs
continuously more than the
permissible number of retries.
Does not accept the received
data, burt the inverter does not
trip.
Does not accept the received
data, but the inverter does not
trip.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fr-a8ers

Table of Contents