• Set 65520 (HFFF0) as a parameter value "8888" and 65535 (HFFFF) as "9999".
• For the instruction codes HFF, HEC and HF3, their values are held once written but cleared to zero when an inverter
reset or all clear is performed.
• When a 32-bit parameter setting or monitored value is read and the read value exceeds HFFFF, the reply data will be
HFFFF.
Example) When reading the C3 (Pr.902) and C6 (Pr.904) settings from the inverter of station No. 0.
Computer send data
a
ENQ 00 FF 0 01 7D
b
ENQ 00 EC 0 01 79
c
ENQ 00 5E 0 0A
d
ENQ 00 60 0 F6
To read/write C3 (Pr.902) or C6 (Pr.904) after inverter reset or parameter clear, execute from (a) again.
Inverter send data
ACK 00
ACK 00
STX 00 0000 ETX 20
STX 00 0000 ETX 20
Description
Set "H01" in the extended link parameter.
Set "H01" in second parameter changing.
C3 (Pr.902) is read. 0% is read.
C6 (Pr.904) is read. 0% is read.
53