Discharge Condensate Installation - Airflow Duplexvent DV65 Entro-V User, Maintenance And Installation Manual

Residential heat recovery units
Table of Contents

Advertisement

8.2. Discharge Condensate Installation

Moisture condensed water should be drained out of the unit, to prevent water damage inside heat recovery
unit and ductwork system.
The following precautions should be observed:
I.
Condensate pipe connections to main drainage line should not be less than the diameter of the drainage outlet
connection (Not less than a diameter of 1/2 inch BSP).
II.
A pipe coupling should be fitted at the pipe connections enabling easy disconnection for service and
maintenance.
III.
Suitable water trap measures should be taken (see below). Pipe runs should slope away from the unit enabling
condensation to drain away.
*Apply a fixing adhesive to the drain
connection part for sealing.
*Install the condensation connection
part in the allocated drainage space.
*Tighten it well by using a spaner.
www.airflow.com
USER
AND MAİNTENANCE MANUAL
9