Name (Model)
When installed in the DC section of the drive unit, the DC reactor improves the power factor and suppresses the input side harmonic current.
 Selection method
Select a DC reactor according to the applied motor capacity.
 Connection diagram
Connect a DC reactor to the drive unit terminals P1 and P. Before
connecting, make sure to remove the jumper across the terminals P1 and
P.
(If the jumper is left attached, no power factor improvement can be
obtained.)
DC reactor (for power
The connection cable between the reactor and the drive unit should be as
short as possible (5m or less).
coordination)
FR-HEL-K
 Outline dimension
Model
0.4K
0.75K
(Note)1. Be sure to remove the jumper across the drive unit terminals P/+ and P1.
(A failure to do so will produce no power factor improving effect)
2. The wiring length between the reactor and drive unit should be within 5m.
3. The size of the cables used should be equal to or larger than that of the power supply
cables (R/L1, S/L2, T/L3).
4. Make a selection according to the motor capacity.
5. Approximately 93% of the power factor improving effect can be obtained (94.4% when calculated with 1 power factor for the fundamental wave
according to the Architectural Standard Specifications (Electrical Installation) (2013 revision) supervised by the Ministry of Land, Infrastructure,
Transport and Tourism of Japan).
6. Outline dimension drawing shown is of a typical model. The shape differs according to each models.
7. Install the DC reactor (FR-HEL) on horizontal or vertical plane.
The EMC Directive compliant EMC filter (EN61800-3 2nd Environment Category C3) is a filter compliant with the EU EMC Directive (EN61800-3 2nd
Environment Category C3).
EMC Filter Model
SF1306
 Depth is 12mm deeper when an intercompatibility attachment is installed.

EMC Directive

 Leakage current for one phase of three-phase three-wire star-connection power supply. Leakage current for
all phases of three-phase three-wire delta-connection power supply is three times greater than the indicated
compliant EMC filter
value.
(Note)This is a sample outline dimension drawing. The shape differs by the model.
SF
 Countermeasures for leakage current
Take the following actions to prevent malfunction of peripheral devices or an electric shock caused by leakage
current.
1) Earth (ground) the EMC filter before connecting the power supply. When doing so, confirm that earthing
(grounding) is securely performed through the earthing (grounding) part of the enclosure.
2) Select an appropriate earth leakage circuit breaker or an earth leakage relay by considering leakage current of the EMC filter. Note that earth
leakage circuit breaker may not be used in some cases such as when leakage current of the EMC filter is too large. In that case, use an earth
leakage relay with high sensitivity. When both of earth leakage circuit breaker and earth leakage relay cannot be used, securely earth (ground) as
explained in 1).
 Outline dimension
Radio noise filter
R S T
FR-BIF
Red White Blue
Specifications, Structure, etc.
(Unit: mm)
Mass
W
D
H
(kg)
70
61
71
0.4
85
61
81
0.5

Outline Dimension

(Unit: mm)
Intercompatibility
Attachment
W
H
110
200
Green
Leakage currents
: 4mA
φ4.3 hole
29
29
7
58
44
(Unit: mm)
Remove the jumper
across terminals P1 and P.
Three-phase
R/L1
AC power
S/L2
supply
T/L3
Leakage
Current
Loss
Mass
(mA)

(W)
(kg)
(Reference
D
Value)
36.5
0.7
10
7.3
Drive unit
MCCB
R/L1
Power
S/L2
supply
T/L3
(Note) 1. Cannot be connected to the drive unit
Earth
Radio noise filter
(Ground)
FR-BIF(-H)
FR-HEL
P1
P
The wiring length should
be 5m at maximum.
Motor
P1
P/+
N/-
U
V
M
W
Drive unit
Less than D
H
W
W
D
output side.
2. Wire should be cut as short as possible,
and connect to the drive unit terminal block.