Terminal Connection Diagram (Speed Control)
Connection example
Sink logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
Control input signals (No voltage input allowed)
Forward
Terminal functions vary
rotation start
with the input terminal
Reverse
assignment (Pr. 178 to Pr.
rotation start
184)
Multi-speed selection
∗2 When using terminals PC
and SD as a 24VDC
power supply, take care
not to short across
terminals PC and SD.
Contact input common
24VDC power supply
(Common for external power supply transistor)
Speed setting signals (Analog)
∗3 Terminal input specifications
can be changed by analog
Speed setting
input specifications
potentiometer
switchover (Pr. 73).
1/2W1kΩ
∗4 It is recommended to use 2W1kΩ
when the Speed setting signal is
changed frequently.
Terminal 4 input
(Current input)
∗5 Terminal input specifications can be changed by analog
input specifications switchover (Pr. 267). Set the
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of Pr.178 to Pr.184 (input terminal function selection)
to assign the function, and turn ON AU signal.
NOTE
· To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
· After wiring, wire offcuts must not be left in the drive unit.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the drive unit clean. When drilling mounting
holes in an enclosure etc., take care not to allow chips and other foreign matter to enter the drive unit.
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1 and P/+.
Earth
(Ground)
Jumper
MC
R/L1
S/L2
T/L3
Earth
(Ground)
STF
STR
RH
High
speed
RM
Middle
speed
RL
Low
speed
MRS
Output
stop
RES
Reset
SD
∗2
PC
10 (+5V)
3
2 0 to 5VDC
2
(0 to 10VDC)
∗4
5 (Analog common)
1
(+)
4 4 to 20mADC
(-)
0 to 5VDC
0 to 10VDC
I
Voltage/current
input switch
Connector for
plug-in option connection
Brake unit
(Option)
∗1
R
∗7
PR N/-
∗6
P1
P/+
V
W
Main circuit
Control circuit
C
B
A
RUN
Running
FU
Speed detection
SE
FM
SD
∗3
PU
connector
∗9
∗5
V
USB
∗5
connector
∗10
Option connector
∗6
A brake transistor is not built-in to the
0.1K and 0.2K.
∗7
Brake resistor (FR-ABR, MRS type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor can not be connected
to the 0.1K and 0.2K.)
PM
motor
Earth (Ground)
Standard control terminal block
Relay output
Terminal functions vary by
Pr. 192 A,B,C terminal
Relay output
function selection
(Fault output)
Open collector output
Terminal functions vary with
the output terminal assignment
(Pr. 190 and Pr. 191)
Open collector output common
Sink/source common
Calibration resistor
Indicator
(Speed meter, etc.)
+
-
Moving-coil type
1mA full-scale
∗8
∗8 It is not necessary when calibrating the
indicator from the operation panel.
∗9 Operation and parameter setting can be
done from the parameter unit (FR-PU07)
and the enclosure surface operation panel
(FR-PA07).
(Use the option cable (FR-CB2
).)
RS-485 communication can be utilized from
a personal computer and other devices.
∗10 A personal computer and a drive unit can
be connected with a USB (Ver1.1) cable.
16