Huawei UPS5000-H Series User Manual page 108

100 kva power module
Hide thumbs Also See for UPS5000-H Series:
Table of Contents

Advertisement

UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module)
Table 10-7 Battery electrical specifications
Item
Battery voltage
(lead-acid
battery)
Battery cold
start
Charger output
power
Battery string
sharing (lead-
acid battery)
Charging
voltage (lead-
acid battery)
Battery type
The UPS supports the SmartLi. For details about the parameters, see the
User Manual .
Table 10-8 Output electrical specifications
Item
Power
system
Voltage
Issue 01 (2020-11-30)
Specifications
360–600 V DC
12 V battery, 30–50 batteries, 0 by default; 40–50 batteries
without derating, 38–39 batteries with output power derated
to 0.9, 34–37 batteries with output power derated to 0.8, or
30–33 batteries with output power derated to 0.7
2 V battery, 180–300 batteries, 0 by default; 240–300 batteries
without derating, 228–239 batteries with output power
derated to 0.9, 204–227 batteries with output power derated
to 0.8, or 180–203 batteries with output power derated to 0.7
NOTE
The number of batteries is 0 by default and needs to be set based on
site requirements. Batteries have no neutral wire, and an odd number
of batteries are supported.
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Under rated conditions, the maximum charge power is 15% of
power of a single module, and the charge current is limited to
30 A.
Supported in a parallel system
● Equalized charging voltage: 2.3–2.4 V/cell; default voltage:
2.35 V/cell
● Float charging voltage: 2.23–2.3 V/cell; default voltage:
2.25 V/cell
● VRLA
● SmartLi
NO TICE
400 kVA
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
Copyright © Huawei Technologies Co., Ltd.
10 Technical Specifications
500 kVA
600 kVA
SmartLi
101