5
UTILITY PACKAGE (GX Configurator-AD)

5.5 Auto Refresh Settings

5 - 15
[Purpose]
Configure the A/D converter module's buffer memory for auto refresh.
[Operating procedure]
"Start I/O No. 1"
Auto refresh
1: Enter the start I/O No. in hexadecimal.
[Setting screen]
[Explanation of items]
(1)
Items
Model side Buffer size
Model side Transfer word count : Displays the number of words to transfer the
Transfer direction
PLC side Device
"Module type"
"Module model name"
: Displays the size of the buffer memory for the
setting item that can be transferred (fixed at
one word).
CPU device from the head device (fixed at
one word).
: " " indicates that data is written from the
device to the buffer memory.
" " indicates that data is read from the buffer
memory to the device.
: Enter a CPU module side device that is to be
automatically refreshed.
Applicable devices are X, Y, M, L, B, T, C, ST,
D, W, R, and ZR.
When using bit devices X, Y, M, L or B, set a
number that can be divided by 16 points
(examples: X10, Y120, M16, etc.)
Also, buffer memory data are stored in a 16-
point area, starting from the specified device
number. For example, if X10 is entered, data
are stored in X10 to X1F.
MELSEC-Q