Operation examples of "Execute test"
The following explains changing CH1 A/D conversion method, from the sampling
processing to Averaging process setting of every ten conversions, and enables
the settings.
(a)
Click the Operating condition setting button on the Monitor/Test screen.
(b)
Change the "setting value" field for "CH1 Averaging process setting" to
"Averaging".
(c)
Change the "setting value" field for "CH1 Time/number of times specifying"
to "Number of times".
(d)
Click the "setting value" field for "CH1 Time/number of times specifying".
(e)
Input "10" as the average number of processing times and press the
Enter
key.
At this point, the setting data have not been written to the A/D converter
module.
(f)
Select the "Setting value" fields input in the operations (b) to (e) while
pressing the
mouse over them.
(g)
Click the
After the completion of writing, the written values are displayed in the
"Current value" field.
At this time, the operation is the same as before changing the setting
value in (b), (c), (d), and (e).
(h)
Set the "Setting value" field of "Operating condition setting request" to
"Setting request".
(i)
Click the
Execute test
"Operating condition setting request" is selected to validate the setting.
Ctrl
key. Multiple fields can be selected by dragging the
Execute test
button to write the data.
button while the "Setting value" field of
MELSEC-Q
5 - 20