Refrigerant piping installation
Type of HR Unit
Select an HR unit according to the number of the indoor units to be installed. HR units are classified into 3 types
by the number of connectable indoor units.
Ex) Installation of 6 indoor units
Consists of HR unit for 4 rooms and HR unit for 2 rooms.
PRHR020(2 rooms)
WARNING
• 1 port of HR unit allows up to 14.1kW based on cooling capacity of the indoor unit (up to 14.1kW
(48kBtu/hr) for max installation).
• The maximum total capacity of the indoor units connected to one PRHR040 HR unit is 47kW
(160kBtu/hr). In case of installation of four indoor units of 14.1kW (48kBtu/hr), use two PRHR020's
rather than one PRHR040.
Low pressure gas pipe
High pressure gas pipe
Liquid pipe
HR unit
Low pressure gas pipe
High pressure gas pipe
Liquid pipe
30
Outdoor Unit
2
1
Remove caps on
the brazing part.
3
2
1
PRHR030(3 rooms)
PRHR020
PRHR030
Ø22.2
Ø19.05
Ø9.52
PRHR040(4 rooms)
1 2
Gas pipe Ø15.88
Liquid pipe Ø9.52
Brazing Type
PRHR040
Ø28.58
Ø28.58
Ø22.2
Ø22.2
Ø12.7
Ø12.7
4
3
1 2
3 4