LG Multi V ARUB Series Installation Manual page 61

Heat recovery outdoor unit
Hide thumbs Also See for Multi V ARUB Series:
Table of Contents

Advertisement

Example of manual valve addressing
(In case that an indoor unit of central control address "11" is connected to a valve #1 of an
HR unit)
• Prerequisite for manual valve addressing: central control address of each indoor unit must be preset differ-
ently at its wired remote control
No.
Display and setup
1
7-SEG
SW01M
2
7-SEG
SW01M
3
7-SEG
SW01M
4
7-SEG
SW01M
5
7-SEG
SW01M
- Above setup must be done for all HR unit valves.
- The valve that is not connected with any indoor unit should be addressed with any other number than used
address numbers of the valves connected with indoor units.
(The valves does not work if the address numbers are same.)
• Operation: None
• Display: None
SW03M
SW04M
• Operation: Turn dip S/W01M No.1 on to address valve #1
• Display: Existing value saved in EEPROM is displayed in
7-SEG.
SW03M
SW04M
• Operation: Set the digit of 10 to the number in Group High data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing left tack S/W03M.
SW04M
• Display: Digit increasing with the times of pressing tack
SW03M
S/W03M is displayed in left 7-SEG
• Operation: Set the digit of 1 to the number in Group Low data
of the wired remote control connected to the corresponding
indoor unit to the valve #1 by pressing right tack S/W04M.
• Display: Digit increasing with the times of pressing tack
SW03M
S/W04M is displayed in right 7-SEG
SW04M
• Operation: Turn dip S/W No.1 off to save the address of
valve #1
• Display: "11" displayed in 7-SEG disappears
SW03M
SW04M
HR Unit PCB
Setup and Contents
Installation Manual 61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents