LG Multi V ARUB Series Installation Manual page 54

Heat recovery outdoor unit
Hide thumbs Also See for Multi V ARUB Series:
Table of Contents

Advertisement

HR Unit PCB
2) Selection of the model of the HR unit
Initial
Setting
1 room
Connected
2 rooms
Connected
3 rooms
Connected
4 rooms
Connected
❈ Each model is shipped with the switches No.2 and No.3 pre-adjusted as above in the factory.
WARNING
• If you want to use a PRHR030 for 2 rooms HR unit after closing the 3rd pipes, set the dip switch for 2 rooms HR unit.
• If you want to use a PRHR040 for 3 rooms HR unit after closing the 4th pipes, set the dip switch for 3 rooms HR unit.
• If you want to use a PRHR040 for 2 rooms HR unit after closing the 3rd and 4th pipes, set the dip switch for 2 rooms HR unit.
• The unused port must be closed with a copper cap, not with a plastic cap.
54
54
Outdoor Unit
Outdoor Unit
2
1
(For 2 rooms)
PRHR020
3
2
1
(For 3 rooms)
PRHR040
4
3
1 2
(For 4 rooms)
PRHR040