LG Multi V ARUB Series Installation Manual page 52

Heat recovery outdoor unit
Hide thumbs Also See for Multi V ARUB Series:
Table of Contents

Advertisement

Electrical Wiring
N Example Connection of Transmission Cable
3 Outdoor Units
I When the power source is connected
In series between the units.
3 phase 4 wires
power supply
Single phase
power supply
I When the power source is supplied to
Each outdoor unit individually.
3 phase 4 wires
power supply
Single phase
power supply
WARNING
• Indoor unit ground lines are required for preventing electrical shock accident in current leakage,
transmission disorder by noise effect and motor current leakage (without connection to pipe).
• Don't install an individual switch or electrical outlet to disconnect each of indoor unit separately from the
power supply.
• All wiring, components and materials to be procured on the site must comply with the applicable local
and national codes.
Between indoor and main outdoor unit
Indoor
Outdoor
unit
unit
HR unit
The GND terminal is a '–' terminal for the central controller, not ground line
52
Outdoor Unit
Power supply switch
(switch fuse)
HR unit
Power supply switch
(switch fuse)
HR unit
Central
controller
Main
outdoor unit
Main
Sub1
Sub2
HR unit
Main
Sub1
Sub2
HR unit
Between main outdoor and sub outdoor unit
Indoor
Outdoor
unit
unit
Outdoor
unit
3 phase 4 wires power line(R, S, T)
Transmission line (3 line): wired remote control
Single phase of power supply line
Transmission line (2 shield line):
between outdoor unit and outdoor unit
Transmission line (2 shield line):
between indoor unit and outdoor unit
Central
Main
controller
outdoor
unit
Outdoor
Sub 1
unit
outdoor
unit
Sub 2
outdoor
unit