LG Multi V ARUB Series Installation Manual page 58

Heat recovery outdoor unit
Hide thumbs Also See for Multi V ARUB Series:
Table of Contents

Advertisement

HR Unit PCB
Flow chart for addressing of indoor and HR Unit
1) Flow chart for Auto addressing
Turn HR unit , indoor unit and outdoor unit on in
the order named.
Wait for 3 minutes
Press SW02M of the outdoor unit main PCB for 5
seconds
'88' is displayed on outdoor unit main PCB and
HRunit PCB
The number of the indoor units connected is
displayed at 7-SEG of the outdoor unit main PCB
after 2~7 minutes
The number of HR units connected is displayed
at 7-SEG of the outdoor unit main PCB
Are the number
of indoor units connected to the outdoor unit
wiring and displayed one equal?
Completion of auto addressing
58
Outdoor Unit
Yes
No
Check power and communication wiring between
outdoor, HR and indoor units
Retry indoor unit auto-addressing after checking
trouble
Incompletion of auto addressing

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents