Technical Specifications - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Motor Modules

5.6 Technical specifications

5.6
Technical specifications
Table 5-7
Technical specifications for the Motor Module, 510 V – 720 V DC
Order number
Rated output current I
N
Base load current I
L
Base load current I
H
Max. output current I
max
kVA rating
1)
Power on basis of I
H
Rated DC link current
Connection voltages
- DC link voltage
- Electronics power supply
Output voltage
Rated pulse frequency
Max. pulse frequency without derating
Max. pulse frequency with derating
Electronics current drain (24 V DC)
Cooling type
DC link capacitance
Power loss
2)
- Air / Coolant
- Total losses
Max. coolant temperature:
- without derating
- with derating
Coolant requirement
3)
Liquid volume of integrated heat exchanger
Typ. pressure drop with volumetric flow
Sound pressure level
DC link/motor connection
Max. connection cross-section
DC link connection (DCP, DCN)
Motor connection (U2, V2, W2)
PE connection
Max. cable length
Degree of protection
Dimensions
Width
Height
Depth
Frame size
Weight
UL listed fuse
5)
Number (connected in parallel)
Rated current
Size acc. to DIN 43620-1
kVA rating refers to the rated motor power of a typical 6-pole motor supplied with 400 V.
1)
At rated pulse frequency
2)
This value applies to both coolant options, i.e. water and water / Antifrogen N mixture with 45 %
3)
Antifrogen N.
This value applies to the water coolant option; for other coolant types, see Chapter 8.
4)
In order to build a UL-approved system, it is absolutely essential to use the specified fuses.
5)
5-14
6SL3325–
1TE33-1AA0
A
310
A
302
A
277
A
453
kW
160
kW
132
A
378
V
DC
V
DC
V
ACeff
kHz
2
kHz
2
kHz
8
A
1.5
Liquid cooling with integrated stainless steel heat exchanger
μF
8400
kW
0.08 / 2.29
kW
2.38
°C
45
°C
50
l/min
12
dm³
0.91
Pa
70000
4)
dB(A)
52
mm²
2 x 240
mm²
2 x 240
mm²
2 x 240
m
IP00
mm
150
mm
1153
mm
545
GXL
kg
80
3NE3 233
1
450
1
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
1TE35–0AA0
490
477
438
715
250
200
598
510 to 720
24 (20.4 – 28.8)
0 to 0.72 x DC link voltage
2
2
8
1.5
9600
0.14 / 3.36
3.74
45
50
12
0.91
70000
52
Flange connection with screws M12
2 x 240
2 x 240
2 x 240
300 (shielded) / 450 (unshielded)
IP00
150
1153
545
GXL
80
3NE3 336
1
630
2