Maintenance and servicing

9.2 Maintenance

9.2
Maintenance
The device comprises mostly electronic components. Apart from the fan(s), therefore, it
contains hardly any components that are subject to wear or that require maintenance or
servicing. Maintenance is intended to ensure that the equipment remains in the specified
condition. Inspections must be performed regularly, but at least once a year. Where
necessary, contaminants must be removed and wearing parts replaced.
The following points must generally be observed.
9.2.1

Cleaning

Dust deposits
Dust deposits inside the device must be removed at regular intervals (or at least once a
year) by qualified personnel in line with the relevant safety regulations. The unit must be
cleaned using a brush and vacuum cleaner, and dry compressed air (max. 1 bar) for areas
that cannot be easily reached.
Ventilation
The ventilation openings in the device must never be obstructed. The fans must be checked
to make sure that they are functioning correctly.
Cable and screw
Cable and screw terminals must be checked regularly to ensure that they are secure in
position, and if necessary, retightened. Cabling must be checked for defects. Defective parts
must be replaced immediately.
Note
The actual intervals at which maintenance procedures are to be performed depend on the
installation conditions (cabinet environment) and the operating conditions.
Siemens offers its customers support in the form of a service contract. For further details,
contact your regional office or sales office.
9-2
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2