Reforming The Dc Link Capacitors - Siemens SINAMICS S120 Equipment Manual

Chassis power units liquid cooled
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

9.5

Reforming the DC link capacitors

Description
If the Basic Line Module and Motor Module are kept in storage for more than two years, the
DC link capacitors have to be reformed. If this is not done, the units could be damaged when
they are operated under load.
If the cabinet is commissioned within two years of its date of manufacture, the DC link
capacitors do not need to be reformed. The date of manufacture is indicated in the serial
number on the type plate (see "Technical Specifications").
Note
The DC link capacitors are reformed by applying the rated voltage without load for at least 30
minutes at room temperature.
Procedure
The DC link capacitors are reformed by applying the rated voltage without load for at least
30 minutes at room temperature.
Type plate
Fig. 9-22
Chassis Power Units Liquid Cooled
SINAMICS S120 Equipment Manual, Edition 04/2007, 6SL3097-2AM00-0BP2
Type plate for an Motor Module
Maintenance and servicing
9.5 Reforming the DC link capacitors
9-47

Advertisement

Table of Contents
loading

Table of Contents