Huawei SmartACBox-12/1-JP User Manual page 57

12-in 1-out smart ac combiner box
Table of Contents

Advertisement

SmartACBox 12-In 1-Out Smart AC Combiner Box
User Manual
LCD
Issue 03 (2018-05-15)
Copyright © Huawei Technologies Co., Ltd.
Operation Procedure
4. Select Comm. Param. and press
Perform step 5 and step 6 to set the
parameters for the RS485.
Perform step 7 and step 8 to set the
parameters for the Ethernet.
5. Select an RS485 port by pressing
and then press
There are three RS485 ports: RS485-1,
RS485-2, and RS485-3.RS485-1–RS485-3
respectively correspond to communications
ports COM1–COM3 on the SmartLogger1000.
6. Set RS485 parameters and then press
The following baud rates are supported:
4800bps, 9600bps, 19200bps and
115200bps. 9600bps is recommended.
1 ≤ Start Address ≤ End Address ≤ 247.
The address segments for these three ports
can overlap.
Set the address scope properly. The
broader the scope is, the longer the time is
for searching the devices.
Parity must be set to the same value for all
devices connected to the same RS485 port.
7. Press
, select Ethernet, and press
6 Operation
.
or
.
.
.
51

Advertisement

Table of Contents
loading