CHAPTER 2
2.1

General Specifications

Item
Operating ambient
temperature
Storage ambient
temperature
Operating ambient
humidity
Storage ambient
humidity
Compliant
Vibration
with JIS B
resistance
3502 and IEC
61131-2
Shock resistance
Operating
atmosphere
Operating
*1
altitude
Installation
location
Overvoltage
*2
category
*3
Pollution degree
Equipment class
*1
Do not use or store the programmable controller under pressure higher than the atmospheric pressure at sea level.
Doing so may cause malfunction.
When using the programmable controller under pressure, please consult your local Mitsubishi representative.
*2
This indicates the section of the power supply to which the equipment is assumed to be connected between the public
electrical power distribution network and the machinery within premises.
Category II applies to equipment for which electrical power is supplied from fixed facilities.
The surge voltage withstand level for up to the rated voltage of 300 V is 2500 V.
*3
This index indicates the degree to which conductive material is generated in terms of the environment in which the
equipment is used.
In pollution degree 2, only non-conductive pollution occurs. A temporary conductivity caused by an accidental
condensation may also occur occasionally.
*4
When setting the transmission clock of the QJ51AW12D2 with a serial number whose sixth digit is 5 or earlier to 125kHz,
use the module within the following specified range.
• Voltage range of external power supply: 21.6 to 25.2VDC
• Operating ambient temperature: 0 to 50
SPECIFICATIONS
5 to 95%RH, non-condensing
Frequency
Under
5 to 8.4Hz
intermittent
8.4 to 150Hz
vibration
5 to 8.4Hz
Under continuous
vibration
8.4 to 150Hz
Compliant with JIS B 3502 and IEC 61131-2 (147 m/, 3 times each in X, Y, and Z directions)
Specifications
*4
0 to 55
25 to 75
Constant
acceleration
9.8m/
4.9m/
No corrosive gas
0 to 2000m
Inside the control panel
II or less
2 or less
Class I

CHAPTER 2 SPECIFICATIONS

Half amplitude
No. of sweeps
3.5mm
10 times each in X,
Y, and Z directions
1.75mm
2
19