Configuration And Project Planning; Configuring The Simatic Rtu3041C - Siemens SIMATIC RTU3041C Manual

Monitoring of remote measurement points
Hide thumbs Also See for SIMATIC RTU3041C:
Table of Contents

Advertisement

2 Engineering
2.2

Configuration and project planning

This section describes the most important steps of the configuration:
Configure the SIMATIC RTU3041C
configuration file
Configuring the TeleControl Server Basic
Configure OPC UA Clients (UaExpert)
2.2.1

Configuring the SIMATIC RTU3041C

This section shows you all necessary steps to configure the RTU3041C for the
application described here.
Note
The supplied project "109739240_RTU3041C_ PROJ_V30.zip" contains the
finished configuration file ("*.cfg"), which you can load into your RTU3041C and
adapt to your application in just a few steps (see
This section is for information only.
Note
Insert a SIM card into the RTU3041C before configuring.
For each RTU, you need a SIM card with data option. You can obtain this from
your mobile provider.
General configuration
1. Connect the RTU3041C to your PG/PC via a network cable.
Note
If you are using multiple RTUs, address conflicts may occur during initial startup
because each RTU is assigned the same IP address by default. Therefore, during
commissioning, ensure that only one RTU is connected to your network at a time.
2. If necessary, change the IP address of your PG/PC (according to
that it and the RTU3041C are in the same subnet.
3. Wake up the RTU3041C by briefly pressing the WKUP/RESET button on the
RTU3041C.
4. In a browser, open the web server of the RTU3041C at the address
"192.168.0.3".
Monitoring of Remote Measurement Points
Entry ID: 109739240,
V3.0,
(Section
2.2.4)
06/2021
(Section
2.2.1) or load the supplied
(Section
2.2.2)
(Section
2.2.3).
Section
2.2.4).
Table
2-1) so
10

Advertisement