2 Engineering
Note
This setting means that the analog input "fillLevel" is only read if the digital input
"enableReadFillLevel" is activated. This can significantly reduce power
consumption.
34. Enable the "Diagnostics messages" to diagnose the errors.
35. Then click "Apply".
36. Open the "Analog memory bits" tab.
37. Click the analog memory bit 0.
38. Enable the "Active" checkbox.
39. Assign the name "maxVolume".
40. Select the type "Analog value".
41. Enter the maximum fill level of the rainwater overflow tank in cubic meters (m³)
as the initial value.
42. Then click "Apply".
43. Click the analog memory bit 1.