Output types include open collector, open collector with pull-ups & line driver. Open collector types
are low cost, have poor noise immunity & can have a maximum wire length of 10 meters. Line driver
outputs have a high speed response, high noise immunity & can be transmitted over a length of 30
meters. A
differential line driver has two signals for each of the outputs. Each signal has a
compliment or inverse (mirror image) referred to as A not, B not & Z not. These can be transmitted
100 meters. Do not connect A not, B not or Z not together or to the + or- side of DC power.
Open Collector Output
Line Driver
Wiring should be shielded cable & should be run through dedicated harnesses or conduits (not
shared with any other wiring) spaced 12 inches apart. Cable assemblies can be ordered from the
encoder manufacturer. Never connect or disconnect the encoder connector or wiring while the power
is on. Doing so may damage the encoder. Do not ground the encoder through both the machine & the
cable wiring. Connect the shield at the input device only. If the shield is connected at both ends,
grounding problems that degrade system performance will result.
Detailed information can be obtained through encoder manufacturers which include BEI, Dynapar &
Lakeshore among others.
Encoders should be selected for specific applications. However, a general recommendation would be
a 1024 PPR, bi-directional, differential line driver output with an index pulse. Power should be 12 or
15 VDC.