Magne 4 Dyn-2Info - ABB Magne 3 Product Manual

Electromagnetic process lock
Table of Contents

Advertisement

5.5

Magne 4 DYN-2Info

Male and female M12 8-pole connectors seen from cable side.
M12 8-pole connector
1
White
2
Brown
3
Green
4
Yellow
5
Grey
6
Pink
7
Blue
8
Red
Warning! The info output is non-failsafe and shall never be used to control a safety
Warning! The DYNlink signal is used to control the safety application.
2TLC172315M0201 Rev.M3
DYNlink signal in
+24 VDC
Locking signal +24 VDC
0 V
Info output (Adam and Eva closed)
DYNlink signal out
0 V
Info output (Locked)
application.