Technical Reference Manual, General
Table 12.6-4 shows which function blocks produce measurement data mapped to the
IEC_103 class 2 measurement frames. This is how the relay configuration is
expected to be implemented. However, if signal types connected to a function block
do not match the following table, corresponding locations in the class 2 frame will
also be replaced by the actual signal types connected to the function block.
7DEOH  )XQFWLRQ EORFNV DQG DYDLODEOH PHDVXUHPHQWV
)% QDPH
MECU1A
Io
MECU1B
Iob
MECU3A
IL1, IL2, IL3
MECU3B
IL1b, IL2b, IL3b
MEFR1
f
MEPE7
P, Q, PF
MEVO1A
Uo
MEVO1B
Uob
MEVO3A
U1, U2, U3, U12, U23, U31
MEVO3B
U1b, U2b, U3b, U12b, U23b, U31b
Available measurements depend on the configuration (e.g. phase voltage
!
or phase-to-phase voltage).
([DPSOH
If the set No 11 is used, the ASDU octets will look like in the following figure:
([DPSOH RQ $6'8 RFWHWV
0HDVXUHPHQWV
1MRS750527-MUM