ABB REF 54 Series Technical Reference Manual page 38

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

5() B

38
)HHGHU 7HUPLQDO
Technical Reference Manual, General
7DEOH 
'LJLWDO LQSXWV DYDLODEOH IRU WKH 5() B
5() 
Digital inputs /
15
total
1)
These digital inputs can be programmed as either digital inputs or pulse counters, refer to section
"Pulse counters" on page 39.
)LOWHU WLPH RI D GLJLWDO LQSXW
The filter time eliminates debounces and short disturbances on a digital input. The
filter time is set for each digital input of the REF 54_ feeder terminal. The operation
of input filtering is illustrated below.
t
0
Input
Filtered Input
Filter Time
)LJ  )LOWHULQJ RI D GLJLWDO LQSXW
In the figure above, the input signal is named 'Input', the filter timer 'Filter Time'
and the filtered input signal 'Filtered Input'. At the beginning, the input signal is at
high state, the short low state is filtered and no input status change is detected. The
low state starting from the time t
change in the input status is detected and the time tag attached to the input change is
t
. The high state starting from t
0
Each digital input has a filter time parameter "Input # filter", where # is the number
of the digital input of the module in question (e.g. Input 1 filter).
3DUDPHWHU
9DOXHV
Input # filter
1....15000 ms
1)
In the feeder terminal revisions of the Release 2.5 or later. Before Release 2.5: 1...65535 ms.
5() 
25
t
1
Filter Time
exceeds the filter time, which means that the
0
is detected and the time tag t
1
'HIDXOW
1)
5 ms
1MRS750527-MUM
5() 
BIO2_7_BI7
BIO2_7_BI8
BIO2_7_BI9
BIO2_7_BI10
34
dipo
is attached.
1