The following values are recommended for the resistor Rh
below:
2SHUDWLQJ YROWDJH 8F
48 V dc
60 V dc
110 V dc
220 V dc
> 20 V
Ic
)LJ 
2SHUDWLQJ SULQFLSOH RI WKH WULS FLUFXLW VXSHUYLVLRQ 7&6 IXQFWLRQ
7HUPLQDO QXPEHUV DUH UHODWHG WR +632
&RQILJXULQJ WKH WULS FLUFXLW VXSHUYLVLRQ &07&6B
The Relay Configuration Tool can be used to connect the trip circuit supervision
input status signals to the function blocks CMTCS1 and CMTCS2. The
configuration of the blocking signal is user-specific and can only be defined in the
feeder terminal configuration. The trip circuit supervision inputs in the feeder
terminal configuration are as follows:
TCS1 and TCS2 inputs in REF 541 and REF 543:
Trip Circuit Supervision 1 input
Trip Circuit Supervision 2 input
TCS1 and TCS2 inputs in REF 545:
Trip Circuit Supervision 1 input
Trip Circuit Supervision 2 input
6KXQW UHVLVWRU 5K
H[W
1.2 k
, 5 W
5.6 k
, 5 W
22 k
, 5 W
33 k
, 5 W
REF 54_
X4.1.10
+ Uc (Operating voltage)
Rh (ext)
X4.1.11
X4.1.12
X4.1.13
*) This is the Circuit Breaker N/O AUX contact
**) This N/C contact enables supervision of N/O AUX contact;
this contact is optional
PS1_4_TCS1
PS1_4_TCS2
PS2_4_TCS1
PS2_4_TCS2
1MRS750527-MUM
in Figure 4.1.11.-1
ext
**)
*)
Rs
TCSfunc
Uc