ABB REF 54 Series Technical Reference Manual page 51

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS750527-MUM
)HHGHU 7HUPLQDO
Technical Reference Manual, General
5HVLVWDQFH VHQVRUV
The resistance sensors may be connected to the RTD/analogue input according to
either the three-wire or the two-wire connection principle. With the three-wire
measuring principle, the wire resistance is automatically compensated. The resistor,
or RTD sensor, is connected across the IN+ and IN- inputs, and the - side of the
resistor/RTD sensor is connected to the GND input. The leads connected to the IN+
and GND inputs must be of the same type.
Re s i s t or s e ns or
)LJ  3ULQFLSOH GLDJUDP RI WKH WKUHHZLUH FRQQHFWLRQ
With the two-wire connection principe, the IN- and GND terminals are linked
together. The resistor is connected across the IN+ and IN- inputs.
Resistor sensor
)LJ  3ULQFLSOH GLDJUDP RI WKH WZRZLUH FRQQHFWLRQ
SHUNT
IN +
IN -
GND
SHUNT
IN +
IN -
GND
5() B
G
mA
+
-
DIFF
resist3w.CNV
G
mA
+
-
DIFF
resist2w.CNV
51