ABB REF 54 Series Technical Reference Manual page 33

Feeder terminal
Hide thumbs Also See for REF 54 Series:
Table of Contents

Advertisement

1MRS750527-MUM


)HHGHU 7HUPLQDO
Technical Reference Manual, General
6FDOLQJ WKH UDWHG YDOXHV RI WKH SURWHFWHG XQLW IRU DQDORJXH
FKDQQHOV
A separate scaling factor can be set for each analogue channel. The factors enable
differences between the ratings of the protected unit and those of the measuring
device (CTs, VTs etc.) The setting value 1.000
protected unit is exactly the same as that of the measuring device.
When scaling factors are used, it should be noted that they affect the operation
accuracy of the terminal. The accuracies stated in the description of each function
block (CD-ROM "Technical Descriptions of Functions") only apply with the default
values of the scaling factors. For example, a high factor affects the operation of
sensitive protection functions such as the directional earth-fault protection.
The scaling factor is calculated channel by channel as follows:
Scaling factor = I
/ I
nmd
np,
I
Rated primary current of the measuring device (A)
nmd
I
Rated primary current of the protected unit connected to the channel
np
Example:
Rated primary current of current trafo = 500 A:
Rated current of the protected unit = 250 A:
Scaling factor for current channels:
The scaling factor is not used for general measurement signals
!
connected to the analogue channel.
The scaling factors for the analogue channels can be set via the HMI of the feeder
terminal or with the Relay Setting Tool. The HMI path for the scaling factors is:
Main Menu/ Configuration/ Protected unit/ Ch 1: scaling,
Ch 2: scaling...
For storing the values listed above, refer to section "Storing of parameters and
recorded data" on page 27.
7HFKQLFDO GDWD RI WKH PHDVXULQJ GHYLFHV
When the feeder terminal is configured, the technical data of the measuring devices
is set in separate dialogue boxes in the Relay Configuration Tool. The set values will
affect the measurements carried out by the feeder terminal.
For storing the values listed below, refer to section "Storing of parameters and
recorded data" on page 27.
1. Prior to the Release 2.5 with two decimals only.
1
means that the rated value of the
where
5() B
I
= 500 A
nmd
I
= 250 A
np
1
500 A / 250 A = 2.000
33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ref 541Ref 542Ref 543Ref 545

Table of Contents