What This Chapter Contains; To Which Drives This Chapter Applies; Description; Category 0 Definition - ABB ACS800 Series Hardware Manual

Hide thumbs Also See for ACS800 Series:
Table of Contents

Advertisement

Category 0 emergency stop for ACS800-02/U2/07/
U7/17/37 (+Q951, R6, R6i, R7, R7i, R8)

What this chapter contains

This chapter describes the category 0 emergency stop function (+Q951). The
chapter deals with applicability, wiring, operation and use. An example circuit
diagram is included.

To which drives this chapter applies

The chapter applies to the following drives:
Drive type
ACS800-02+C111
ACS800-02+C127
ACS800-U2
ACS800-07
ACS800-U7
ACS800-17
ACS800-37

Description

Category 0 definition

IEC/EN 60204-1 defines category 0 emergency stop as a stop by immediate
removal of power to machine actuators.

Implementation of category 0 stop in ACS800 in brief

The category 0 emergency stop opens the line contactor switching off the supply
power. The motor coasts to stop.
Category 0 emergency stop for ACS800-02/U2/07/U7/17/37 (+Q951, R6, R6i, R7, R7i, R8)
Frame sizes
Option codes and descriptions
R7, R8
+F250+Q951 = line contactor + category 0 emergency stop
R6, R7, R8
R6i, R7i
17

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs800-02Acs800-u2Acs800-07Acs800-u7Acs800-17Acs800-37

Table of Contents